ADHESIVES PLANT WASTEWATER TREATMENT RESULTS
The adhesives manufacturing facility in Lower Mainland was using conventional
chemistry to treat the rinse water generated from cleaning process reactors.
They manufacture 40 different types of water-based adhesives. The process
operates in 2000 Gallon batches, treated water is filtered with a filter-press
before going into sewer. The system used polyol 601 (coagulant), caustic (sodium
hydroxide) and anionic polymer (flocculant). The treated water was inconsistent
in quality & zinc levels due to variations in wastewater constituents depending
on production.
Another major problem was frequent blinding of filter press cloth
leading to inefficient dewatering of sludge (sloppy sludge). They had to clean
the filter cloths & press with a pressure washer every other batch (sometimes
every batch) and cleaning process took approx 2 – 3 hours.
Simran
Canada surveyed the wastewater treatment
facility and conducted tests with various chemicals. Best results were achieved
by using caustic and Floccin-A. The Floccin products are a “One Chemical”
treatment that replaces coagulants, pH control (to some extent), flocculants and
filtering-aids. They started using Floccin-A in November, 2004 and the results
speak for themselves.
Benefits: Since November 2004, there has been no need for pressure
washing due to sloppy sludge, quality of treated water is consistent, sludge
volume has reduced by approx 50% due to drier cake, no need for DE pre-coat,
overall chemical cost is same and significant savings in man-hours.
Comparison:
|
Before
|
After
|
|
Needed 3 chemicals: Polyol 601, Sodium hydroxide and Polymer.
|
Using 2 chemicals: Sodium hydroxide & Floccin-A.
|
|
Filter Press: 2 full presses per batch.
|
Filter Press: 1 full presses per batch.
|
|
Frequent need to pressure-wash filter cloth & press due to sloppy sludge caused
by blinding of filter cloth.
|
No need
for pressure washing due to sloppy sludge since November, 2004 because of unique
chemistry.
|
|
Need to prepare polymer batch
|
No need
|
Note: This facility was shut-down in 2009 due to economic
restructuring.
|